GENERAL DATA
- Output rated power 6000VA /6000W
- Output power factor 1
- Topology Online double conversion
- Internal Batteries 2U: N.A.; 4U: YES
- Parallel Configuration Up to 4 units
INPUT
- Voltage range 110~280 Vac (Single + G)
- Frequency range 45-70Hz (auto sensing)
- Input power factor ≥ 0.99 @ 100% linear load
- Input Current Distorsion ≤ 3% (full load)
OUTPUT
- Output voltage 200/208/220/230/240 Vac (Single + G)
- Output voltage distortion <1%@100% Linear Load; <3% @100% Non-Linear Load
- Output voltage regulation ±1%
- Frequency range ±1Hz or ±3Hz (selectable)
- Crest factor ‘3:1
- Output waveform Pure sine wave
- Overload Capacity Inverter
<105%continuous
105-125% for 600 to 30 seconds transfer to bypass.
125-150% for 30 seconds to immediately transfer
to bypass.
EFFICIENCY
- Line Mode 94%
- High Efficiency Mode ≥98%
BATTERY
- Type VRLA Maintanance Battery
- Charging Current 2 A
- Recharge time (to 90%) 4 hours
- Part Number
00-00437 - Product Name
UPS-EP006-11-I20-4U

Reviews
There are no reviews yet.